Modbus is simple and found everywhere: in frequency drives, energy meters, sensors and simple PLCs. Precisely because of that simplicity, things often go wrong in the details. These are the most common pitfalls.
The four register types
- Coils: bits you can read and write.
- Discrete inputs: bits you can only read.
- Input registers: 16-bit values you can only read.
- Holding registers: 16-bit values you can read and write.
Shifted by one register
The most common mistake: all values are one place off. The cause is that the manufacturer’s manual counts from 1, or from 40001, while the protocol counts from 0. Lower the address by 1, or drop the 4xxxx prefix.
Absurdly large numbers
A 32-bit value, such as an int32 or a float, takes up two registers. The order of those two words differs per manufacturer. If the order is wrong, you get huge or meaningless numbers. Then swap the word order.
Ten times too large
Many devices deliver tenths or hundredths, so they don’t need a decimal point. A current of 12.4 A then arrives as 124. A scale of 0.1 gets you to the real unit. Sometimes an offset is needed too: value times scale plus offset.
Unit ID behind a gateway to RTU
If there is a gateway between the network and a serial Modbus RTU bus, you have to enter the unit ID of the device behind the gateway. Otherwise you get a timeout.
Start with the register map
Always ask for the manufacturer’s register map before you start. It lists the register type, address, data type and scale for each value.